DC Immunity Current Transformers KLS11-CT-007

DC Immunity Current Transformers  KLS11-CT-007
  • small-img

Please download PDF information:


pdf

Product Detail

Product Tags

Product Images

DC Immunity Current Transformers DC Immunity Current Transformers

Product Information

DC Immunity Current Transformers
With copper bracket 
(Other sizes can be OEM)

Application to single-phase or three-phase electronic type electric energy meter.

Main characteristics:
1. Adopt high magnetic permeability magnetic core,with high precision and good linearity.
2.The range of applicable electric current is wide(1.5A-120A)
3. Primary input and secondary output ensures flexible and diversified forms as well as easy installation.
4. Frequency: 50Hz/60Hz
5. Ambient Temperature: -40℃ — 70℃
6. With a complete range of specifications(See the following table for details),products can be made according to customers’ special requirements.

1.Dimension Data:

CT Main Dimension (mm) Wire (mm)
Primary Current
(A)
A (Inner Hole) B (Out Diameter) C (Thickness) Length End Tinned
6A~60A 0 26±1 15 100 5

2. Specifications

CT
Current Rati
Ratio Load Resistance(Ω) Accuracy Class Phase error Insulation voltage
Model NO.
Primary Current
(A)

Secondary current( mA )

Turns Turns
CT007 1.5(6A) 1.5 / 5.0 1:2000 1:2500 5/10/20Ω 0.1/ 0.2 <15′ 3000V
CT007 2.5(10)A 2.5 / 5.0 1:2000 1:2500 5/10/20Ω 0.1/ 0.2 <15′ 3000V
CT007 5(20)A 2.5 / 5.0 1:2000 1:2500 5/10/20Ω 0.1/ 0.2 <15′ 3000V
CT007 5(30)A 2.5 / 5.0 1:2000 1:2500 5/10/20Ω 0.1/ 0.2 <15′ 3000V
CT007 5(40)A 2.5 / 5.0 1:2000 1:2500 5/10/20Ω 0.1/ 0.2 <15′ 3000V
CT007 5(50)A 2.5 / 5.0 1:2000 1:2500 5/10/20Ω 0.1/ 0.2 <15′ 3000V
CT007 5(60)A 2.5 / 5.0 1:2000 1:4000 5/10/20Ω 0.1/ 0.2 <15′ 3000V

  • Previous: